Product Lists
Product Search
Product show
GHR16 One Module 6KA RCBO
PDF Download

 
  Standard   IEC/EN 61009-1
Electrical features Mode   Electronic type
Type(wave form of the earth leakage sensed)   AC
Thermo-magnetic release characteristic   B,C
Rated current In A 2,4,6,10,16,20,25,32,40
Poles P 1P+N N-Pole break
Rated voltage Ue V AC 240
Rated sensitivity I¡÷n A 0.01,0.03,0.1
Rated residual making and breaking capacity I¡÷m A 500
Rated short-circuit capacity Icn A 4500,6000
Break time under I¡÷n s ¡Ü0.1
Rated frequency Hz 50/60
Rated impulse withstand voltage(1.2/50)Uimp V 4000
Dielectric test voltage at ind.Freq.for 1min kV 2
Insulation voltage Ui   500
Pollution degree   2
Mechanical features Electrical life t 4000
Mechanical life t 4000
Contact position indicator   Yes
Protection degree   IP20
Ambient temperature(with daily average¡Ü35¡æ) ¡æ -5~+40(Special application please refer
to temperature compensation correction)
Storage temperature ¡æ -25~+70
Installation Terminal connection type   Cable/U-type busbar/Pin-type busbar
Terminal size top/bottom for cable mm2 16
AWG 18-5
Terminal size top/bottom for busbar mm2 16
AWG 18-5
Tightening torque N*m 2
In-Ibs. 18
Mounting   On DIN rail EN 60715(35mm)by means of fast clip device
Connection   From top
Wiring Diagram
Overal and mounting dimensions(mm)