Combined electronic residual current device 1P+N
Combined electronic residual current device 3P + N
Geometrical dimensions |
L(mm) |
1P+N |
2P |
3P |
3P+N |
H(mm) |
44
95 |
62
95 |
88
95 |
115.5
95 |
|
|
Description of the Operating System
It is a combination of automatic circuit breaker and residual current electromagnetic device.It combines part of the properties of the two elements.The circuit breaker reacts at short circuit in the protected circuit,and the electromagnetic residual current device -at failure in the conductors " insulation.
STANDARDS:EN60898-1 EN61009-1 EN61009-2 EN60947-1
Functions
¡ö switching off heavy-loaded electrical circuits at short circuit or overload
¡ö switching off heavy-loaded electrical circuits at insulation damage of the conductors to consumers
¡ö switching off heavy-loaded electrical circuits at presence of a person under voltage
¡ö used to protect not only particular consumers/circuits,but also the whole panel
¡ö remarkable with high reliability of current characteristics
¡ö control:manual switching on and automatic switching off at exit failure
Technical Date
*Rated operating voltage:230/400V 50Hz
*Residual current responsiveness:30;100;300;500mA
*Time delay until break:
-of the residual current device:<0.1s at l? n and <0.04s at 2l ? n
-of the circuit breaker:<0.1s
*Circuit breaker breaking curve :C
*Surge voltage wear resistance:?2000V
*Breaking capacity:4500A
Type
designation |
Number of poles of
the residual current
device/circuit breaker |
Breaking capacity
(kA) |
Sections of the mounting conductors (mm2) |
Rated current
(A) |
Package/Box
(pcs) |
C41LE C10 |
2 |
4.5 |
1.5 |
10 |
7/140 |
C41LE C16 |
2 |
4.5 |
2.5 |
16 |
7/140 |
C41LE C25 |
2 |
4.5 |
4.0 |
25 |
7/140 |
C41LE C40 |
2 |
4.5 |
10.0 |
40 |
7/140 |
C41LE C50 |
2 |
4.5 |
16.0 |
50 |
7/140 |
|
C42LE C10 |
2 |
4.5 |
1.5 |
10 |
5/100 |
C42LE C16 |
2 |
4.5 |
2.5 |
16 |
5/100 |
C42LE C25 |
2 |
4.5 |
4.0 |
25 |
5/100 |
C42LE C40 |
2 |
4.5 |
10.0 |
40 |
5/100 |
C42LE C50 |
2 |
4.5 |
16.0 |
50 |
5/100 |
Type
designation |
Number of
poles of the residual
current device/circuit breaker |
Breaking capacity
(kA) |
Sections of
the mounting conductors
(mm2) |
Rated
current
(A) |
Package/Box
(pcs) |
C43LE C10 |
3 |
4.5 |
1.5 |
10 |
3/60 |
C43LE C16 |
3 |
4.5 |
2.5 |
16 |
3/60 |
C43LE C25 |
3 |
4.5 |
4.0 |
25 |
3/60 |
C43LE C40 |
3 |
4.5 |
10.0 |
40 |
3/60 |
C43LE C50 |
3 |
4.5 |
16.0 |
50 |
3/60 |
Type
designation |
Number of poles of
the residual current
device/circuit breaker |
Breaking capacity
(kA) |
Sections of
the mounting conductors
(mm2) |
Rated
current(A) |
Package/Box
(pcs) |
C44LE C10 |
4 |
4.5 |
1.5 |
10 |
2/40 |
C44LE C16 |
4 |
4.5 |
2.5 |
16 |
2/40 |
C44LE C25 |
4 |
4.5 |
4.0 |
25 |
2/40 |
C44LE C40 |
4 |
4.5 |
10.0 |
40 |
2/40 |
C44LE C50 |
4 |
4.5 |
16.0 |
50 |
2/40 |
|