Product Lists |
|
|
|
Product Search |
|
Product show |
|
GHR21EW-40 Residual Current Circuit Breaker with Over Current Protection |
PDF Download |
|
|
|
Standard |
|
IEC/EN 61009 |
Electrical features |
Mode |
|
Electronic type |
Type(wave form of the earth leakage sensed) |
|
AC |
Thermo-magnetic release characteristic |
|
B,C |
Rated current In |
A |
2,4,6,10,16,20,25,32,40 |
Poles |
P |
1P+N N-Pole break |
Rated voltage Ue |
V |
AC 230 |
Rated sensitivity I¡÷n |
A |
0.01,0.03,0.1 |
Rated residual making and breaking capacity I¡÷m |
A |
500 |
Rated short-circuit capacity Icn |
A |
4500 |
Break time under I¡÷n |
s |
¡Ü0.1 |
Rated frequency |
Hz |
50/60 |
Rated impulse withstand voltage(1.2/50)Uimp |
V |
4000 |
Dielectric test voltage at ind.Freq.for 1min |
kV |
2 |
Insulation voltage Ui |
V |
250 |
Pollution degree |
|
2 |
Mechanical features |
Electrical life |
|
4000 |
Mechanical life |
|
4000 |
Fault current Indicator |
|
Yes |
Protection degree |
|
IP20 |
Ambient temperature(with daily average¡Ü35¡æ) |
¡æ |
-5~+40(Special application please refer to temperature compensation correction) |
Storage temperature |
¡æ |
-25~+70 |
Installation |
Terminal connection type |
|
Cable/Pin-type busbar/U type busbar |
Terminal size top/bottom for cable |
mm2 |
16 |
AWG |
18-3 |
Terminal size top/bottom for busbar |
mm2 |
25 |
AWG |
18-3 |
Mounting |
|
On DIN rail EN 60715(35mm)by means of fast clip device |
Connection |
|
From top | |
Wiring Diagram |
|
Overal and mounting dimensions(mm) |
| | |
|
|
|